EPA 608 Cheat Sheet: Key Numbers, Important Dates, Definitions and Commonly Missed Concepts
Preparing for the EPA Section 608 certification examination becomes easier when you organize important facts into manageable groups. The examination includes environmental science, federal regulations, refrigerant recovery requirements, equipment classifications, safety principles, and technical definitions.
Many candidates struggle because similar numbers appear in different regulatory contexts. A recovery percentage may look like a cylinder filling limit, while an appliance charge threshold may be confused with a leak repair percentage.
This EPA 608 cheat sheet brings together essential examination concepts in one practical study guide.
Use it alongside full study materials and original practice questions. Memorizing numbers is helpful, but understanding when each number applies is equally important.
Check the current EPA rules for changes, particularly when studying leak repair, HFC management, refrigerant sales, and recordkeeping requirements.
EPA 608 Exam Format Cheat Sheet
The standard proctored EPA 608 examination contains four sections.
- Core: 25 questions.
- Type I: 25 questions.
- Type II: 25 questions.
- Type III: 25 questions.
- Complete Universal examination: 100 questions.
- Standard proctored passing score: 18 out of 25 per required section.
- Equivalent standard passing percentage: 72 percent.
Certain approved open-book Type I examination arrangements generally require 21 correct answers out of 25 in each required section, equivalent to 84 percent.
Universal certification requires successful completion of all four sections under qualifying testing conditions.
An open-book Core examination generally cannot count toward Universal certification.
Section 608 technician certification does not normally expire.
EPA 608 Certification Types
Remember the relationship between certification categories and equipment.
Core: Environmental protection, regulations, refrigerant management, safety, and refrigeration fundamentals.
Type I: Small appliances meeting the applicable factory manufacturing, charging, sealing, and refrigerant quantity requirements.
Type II: High-pressure and very-high-pressure appliances, excluding small appliances and motor vehicle air conditioners covered separately.
Type III: Low-pressure appliances, including certain centrifugal chillers.
Universal: All three equipment certification categories, supported by successful completion of Core.
Section 609: A separate certification framework associated with motor vehicle air conditioning service.
Universal certification does not automatically include Section 609 certification.
Important Refrigerant Charge Thresholds
Several refrigerant quantities appear frequently in EPA 608 study material.
Five pounds: The maximum refrigerant charge associated with the federal small appliance definition.
The appliance must also satisfy the relevant factory manufacturing, charging, and hermetic sealing requirements.
15 pounds: The traditional maximum appliance charge for using system-dependent recovery equipment.
This number also appears in newer HFC management regulations, but those requirements involve a separate regulatory context.
50 pounds: The traditional minimum full charge for covered appliances subject to Section 608 ozone-depleting refrigerant leak repair requirements.
200 pounds: An important dividing point in the traditional evacuation requirements for high-pressure and medium-pressure appliances.
500 pounds: An important charge threshold for certain periodic leak inspection requirements involving covered commercial refrigeration and industrial process refrigeration appliances.
Do not treat these numbers as universal requirements that apply to every refrigerant and appliance.
Small Appliance Recovery Percentage Cheat Sheet
For Type I small appliances, the standard recovery percentage depends on the recovery equipment manufacturing date and, in some cases, compressor operation.
Recovery equipment manufactured before November 15, 1993:
- Recover at least 80 percent of the refrigerant.
Recovery equipment manufactured on or after November 15, 1993:
- Operating appliance compressor: recover at least 90 percent.
- Nonoperating appliance compressor: recover at least 80 percent.
An alternative method of satisfying the applicable small appliance recovery requirement is evacuation to four inches of mercury vacuum.
A useful memory aid is that newer recovery equipment combined with an operating compressor produces the higher percentage requirement.
The 80 percent small appliance recovery requirement is unrelated to the commonly used 80 percent recovery cylinder liquid filling limit.
EPA 608 Evacuation Level Cheat Sheet
The traditional federal recovery evacuation table distinguishes between recovery equipment manufactured before November 15, 1993, and equipment manufactured on or after that date.
For very-high-pressure appliances:
- Older equipment: 0 inches of mercury vacuum.
- Newer equipment: 0 inches of mercury vacuum.
For high-pressure appliances containing below 200 pounds:
- Older equipment: 0 inches of mercury vacuum.
- Newer equipment: 10 inches of mercury vacuum.
For high-pressure appliances containing 200 pounds or more:
- Older equipment: 4 inches of mercury vacuum.
- Newer equipment: 15 inches of mercury vacuum.
For medium-pressure appliances containing below 200 pounds:
- Older equipment: 4 inches of mercury vacuum.
- Newer equipment: 10 inches of mercury vacuum.
For medium-pressure appliances containing 200 pounds or more:
- Older equipment: 4 inches of mercury vacuum.
- Newer equipment: 15 inches of mercury vacuum.
For low-pressure appliances:
- Older equipment: 25 millimeters of mercury absolute.
- Newer equipment: 25 millimeters of mercury absolute.
These values describe standard recovery requirements. Regulatory exceptions may apply.
Do not confuse them with the deeper vacuum levels used for system dehydration.
Leak Repair Threshold Cheat Sheet
The traditional Section 608 leak repair framework generally applies to covered appliances containing at least 50 pounds of ozone-depleting refrigerant.
The commonly tested annualized leak rate thresholds are:
- Comfort cooling and other covered appliances: 10 percent.
- Commercial refrigeration: 20 percent.
- Industrial process refrigeration: 30 percent.
An easy memory aid is 10, 20, 30, progressing from comfort cooling to commercial refrigeration to industrial process refrigeration.
Older materials may list historical thresholds of 15 percent and 35 percent.
These historical figures should not be confused with the revised requirements.
Separate AIM Act refrigerant management rules apply to certain HFC-containing appliances and substitutes, including qualifying appliances with charges of 15 pounds or more.
Check current EPA requirements to determine which framework applies.
Leak Repair Deadlines and Reporting Numbers
Important traditional Section 608 leak repair numbers include:
- 30 days: Standard repair deadline after applicable requirements are triggered.
- 120 days: Potential repair period for qualifying industrial process refrigeration repairs requiring a process shutdown.
- 10 days: Common follow-up verification testing timeframe under specified conditions.
- 30 days: Common timeframe for developing a required retrofit or retirement plan.
- One year: Standard timeframe for completing an applicable retrofit or retirement plan, subject to exceptions.
- 125 percent: Annual refrigerant loss threshold associated with certain chronic leak reporting requirements.
- March 1: Traditional deadline for reporting qualifying chronic refrigerant losses from the preceding calendar year.
Covered commercial refrigeration and industrial process refrigeration appliances containing 500 pounds or more may require quarterly leak inspections under applicable conditions.
Smaller covered appliances and comfort cooling equipment generally have annual inspection requirements under the relevant framework.
Many Section 608 records must be retained for three years.
Each deadline has specific applicability conditions. Memorize the conditions as well as the number.
Important EPA 608 Dates
Several historical dates help explain the development of refrigerant regulations.
1987: Adoption of the Montreal Protocol.
1989: Entry into force of the Montreal Protocol.
1990: Clean Air Act Amendments established major federal ozone protection provisions.
July 1, 1992: The federal prohibition on intentional venting of ozone-depleting refrigerants during covered servicing and disposal activities took effect.
November 15, 1993: Important manufacturing date dividing traditional recovery equipment requirements.
November 14, 1994: Key technician certification compliance date under the original Section 608 framework.
November 15, 1995: Venting restrictions were extended to many substitute refrigerants.
January 1, 1996: Production and import of many CFCs for ordinary uses were phased out in the United States.
2016: Adoption of the Kigali Amendment addressing HFC phasedown.
January 1, 2018: Major expanded Section 608 technician certification and refrigerant sales requirements involving substitute refrigerants took effect.
January 1, 2019: Revised Section 608 leak repair thresholds became applicable.
January 1, 2020: Ordinary production and import of newly manufactured R-22 ended in the United States.
April 10, 2020: Federal changes removing substitute-only appliances from traditional Section 608 leak repair provisions took effect.
2020: Enactment of the American Innovation and Manufacturing Act.
2026: Major leak repair provisions under the separate AIM Act refrigerant management framework began applying to certain covered appliances.
Historical dates explain regulatory development. They should not replace current compliance information.
Refrigerant Environmental Definitions
CFC: Chlorofluorocarbon. Contains chlorine, fluorine, and carbon. Generally associated with significant ozone depletion potential.
HCFC: Hydrochlorofluorocarbon. Contains hydrogen, chlorine, fluorine, and carbon. Generally has lower ODP than comparable CFCs but still contributes to ozone depletion.
HFC: Hydrofluorocarbon. Contains hydrogen, fluorine, and carbon. Generally has zero ODP, although many HFCs have substantial GWP.
HFO: Hydrofluoroolefin. An unsaturated fluorinated refrigerant family containing substances that commonly have relatively low GWP.
ODP: Ozone depletion potential. R-11 is the traditional reference substance with an ODP of 1.
GWP: Global warming potential. Carbon dioxide is the reference substance with a GWP of 1.
Stratospheric ozone: Atmospheric ozone that helps protect the Earth's surface from harmful ultraviolet radiation.
Remember that zero ODP does not automatically mean zero GWP.
Recovery, Recycling and Reclamation Definitions
These three definitions should be memorized accurately.
Recover: Remove refrigerant from an appliance and store it in an external container without necessarily processing it.
Recycle: Clean recovered refrigerant by reducing contaminants through appropriate processes for permitted reuse.
Reclaim: Process refrigerant to applicable purity specifications and verify that it meets those specifications.
Recovery does not automatically clean refrigerant.
Recycling does not automatically satisfy reclamation standards.
Reclamation is generally required before used refrigerant is transferred for use by a different owner when the applicable federal restrictions require it.
Recovery Cylinder Safety Cheat Sheet
Important cylinder concepts include:
- Recovery cylinders must be refillable and appropriately approved.
- Disposable cylinders must not be refilled.
- Recovery cylinders commonly have a gray body and yellow shoulder.
- Color alone does not establish cylinder suitability.
- Cylinder liquid filling is commonly limited to approximately 80 percent of volume.
- Refrigerant expands as temperature increases.
- Cylinders must have appropriate pressure ratings.
- Different refrigerants should not be mixed.
- Refrigerant quantities should be monitored using suitable weighing equipment.
A five-year cylinder requalification interval is commonly encountered in examination materials, but actual requirements depend on cylinder specifications and applicable transportation regulations.
Never assume that a cylinder is suitable simply because it resembles another recovery cylinder.
Pressure and Vacuum Numbers
Important pressure reference values include:
- Standard atmospheric pressure: approximately 14.7 psia.
- Standard atmospheric pressure: approximately 29.92 inches of mercury absolute.
- Standard atmospheric pressure: approximately 760 millimeters of mercury absolute.
- One millimeter of mercury: approximately 1,000 microns of mercury.
- Zero psig: atmospheric pressure.
- Zero psia: perfect vacuum.
The standard Type III recovery level of 25 millimeters of mercury absolute is equivalent to approximately 25,000 microns.
This is not the same as 25 microns.
A commonly encountered system dehydration target is 500 microns, but this is not a universal EPA refrigerant recovery requirement.
Refrigeration Cycle Cheat Sheet
The four main vapor-compression refrigeration components perform different functions.
Compressor: Raises refrigerant vapor pressure and circulates refrigerant.
Condenser: Rejects heat and commonly converts refrigerant vapor into liquid.
Expansion device: Reduces refrigerant pressure and controls refrigerant flow.
Evaporator: Absorbs heat and commonly converts liquid refrigerant into vapor.
Remember that the condenser rejects heat while the evaporator absorbs heat.
The compressor is generally designed to compress vapor, not large quantities of liquid refrigerant.
Liquid entering a compressor not designed to handle it can cause mechanical damage.
Refrigerant Blend Definitions
A refrigerant blend contains more than one refrigerant component.
An azeotropic blend behaves approximately like a single refrigerant during phase changes under relevant conditions.
A zeotropic blend may experience temperature glide during evaporation and condensation.
Temperature glide is the difference between relevant bubble-point and dew-point temperatures at a given pressure.
Fractionation occurs when the composition of a blend changes because its components evaporate or condense differently.
For blends with temperature glide:
- Dew-point temperature is generally used for superheat calculations.
- Bubble-point temperature is generally used for subcooling calculations.
Follow manufacturer instructions when charging refrigerant blends. Many blends are transferred from supply cylinders as liquid to help preserve their intended composition.
Commonly Missed EPA 608 Concepts
Candidates should pay special attention to these frequently confusing distinctions.
Small appliance versus small refrigerant charge: A low refrigerant charge alone does not establish that equipment meets the small appliance definition.
Recovery versus evacuation: Removing refrigerant and preparing a repaired system for charging are different operations.
Gauge versus absolute pressure: Zero gauge pressure is not a perfect vacuum.
Low-pressure leaks: Air may enter equipment operating below atmospheric pressure.
Purge units: These remove noncondensable gases but do not replace leak repairs.
Venting exceptions: Limited exceptions do not authorize unrestricted refrigerant release.
Phaseout versus equipment ban: Ending ordinary refrigerant production does not automatically prohibit operating existing equipment.
Certification versus licensing: Section 608 certification does not replace every state or local HVAC licensing requirement.
Traditional versus newer leak rules: Section 608 ozone-depleting refrigerant requirements and AIM Act refrigerant management requirements must be distinguished.
How to Review This EPA 608 Cheat Sheet
Start by reviewing the definitions without looking at their explanations.
Next, write down the important numbers and identify the conditions attached to each one.
Practice recalling the recovery requirements for older and newer equipment.
Review the differences between inches of mercury vacuum, millimeters of mercury absolute, and microns.
Complete practice questions covering all four examination sections.
Whenever you answer incorrectly, identify whether the mistake involved a forgotten fact, incorrect equipment classification, misunderstood regulation, or measurement unit.
Focus additional study time on the reason behind each mistake.
This approach helps you develop understanding rather than relying entirely on memorization.
Frequently Asked Questions
What is the most important number to remember for Type I?
Five pounds is the maximum charge associated with the small appliance definition. Recovery percentages of 80 and 90 percent are also important.
What are the main Type II evacuation numbers?
For high-pressure appliances using qualifying newer recovery equipment, remember 10 inches of mercury vacuum below 200 pounds and 15 inches at 200 pounds or more.
What is the Type III evacuation requirement?
The standard recovery-table requirement is 25 millimeters of mercury absolute.
What are the traditional leak repair thresholds?
Remember 10 percent for comfort cooling and other covered appliances, 20 percent for commercial refrigeration, and 30 percent for industrial process refrigeration.
What does the 80 percent cylinder rule mean?
It refers to the commonly used maximum liquid-volume filling limit that leaves room for thermal expansion.
Is memorizing this cheat sheet enough to pass?
A cheat sheet is useful for revision, but candidates should also understand technical concepts, regulatory conditions, safety principles, and equipment classifications.
Are EPA 608 examination rules always the same?
No. Regulations and examination materials can change. Check the current EPA rules and approved certification organization requirements before testing.
Does Universal certification expire?
EPA Section 608 Universal certification does not normally expire, but technicians must continue following current refrigerant management regulations.
Practise what you just read
More study guides
- How to Pass the EPA 608 Certification Exam: Complete Study Guide
- EPA 608 Refrigerant Recovery Rules, Evacuation Levels and Recovery Cylinders Explained
- EPA 608 Leak Repair Thresholds, Recordkeeping and Technician Certification Records
- EPA 608 Environmental Study Guide: Ozone Depletion, Montreal Protocol, Clean Air Act, ODP and GWP
- EPA 608 Type II vs Type III: High-Pressure and Low-Pressure Refrigeration Systems Explained